Specification:
Target Gas & Sensor: Detects propane (0–20% LEL) using a semiconductor sensor with natural diffusion detection.
Alarm & Response: Alarm point at 10% LEL; response time ≤30s; warming time 130s ±10s; sound and light alarm ≥75dB.
Power & Consumption: AC 110V ±6%, 60Hz; power consumption <4W; includes 1 active AC output and 1 free contact output (NO/NC).
Operating Conditions: Temperature -10℃~55℃, humidity ≤95% RH, indoor use, atmospheric pressure 86–106 kPa.
Design & Lifespan: Compact and lightweight (210g), dimensions 115×88×37mm; sensor life 5 years under normal conditions; compliant with BS EN50194:2000.